13
that drives the suction pressure below cutout conditions).
Hydronic side limits in cooling fall into the 25
o
F entering
water temperature range.
VII. ELECTRICAL SERVICE
The main electrical service must be protected by a fuse or
circuit breaker, and be capable of providing the amperes
required by the unit at nameplate voltage. All wiring
shall comply with the national electrical code and/or any
local codes that may apply. Access to the line voltage
contactor is gained through the knockouts provided on
either side of the heat pump next to the front corner.
Route EMT or flexible conduit with appropriate 3-
conductor wire to the contactor.
1WARNING - The unit must be properly grounded!1
,CAUTION: Three-phase units MUST be wired
properly to insure proper compressor rotation. Improper
phasing may result in compressor damage. An electronic
phase sequence indicator must be used to check supply-
wiring phase. Also, the “Wild” leg of the three-phase
power must be connected to the middle leg on the
contactor.
When supplying power to external water pumps with the
heat pump’s power supply, use only impedance protected
motors. An ECONAR PumpPAK can be wired directly
to the contactor and grounded in the grounding lug. A
pump relay and a terminal block (BP) are supplied in the
electrical box for the hydronic side pump (not available
on GW380’s). The relay will start the pump with a call
from the aquastat or thermostat. The pump relay is
activated by power to Y on the terminal strip of hydronic
units (wire Y to X). The use of impedance protected
pumps eliminates the need for additional fusing. Do not
connect more than a 1/3 horsepower pump to the internal
pump relay.
If larger pumps are required, a separate power supply is
required to supply the pump. To start this pump use a 24-
volt relay pulled in from the Y and X terminals.
VIII. 24 VOLT CONTROL
CIRCUIT
The wiring diagrams in Figures 7 and 8 show the low
voltage controls of the heat pump and some generic
external control schemes. This section will break down
the three basic components of the low voltage circuit;
transformer, thermostat/aquastat, and controller.
A. Transformer
Electrical diagrams are provided in Figures 7 and 8, and
also on the electrical box cover panel of the heat pump.
An internal 24-volt, 55 VA transformer (100 VA on
GW380’s) is provided to operate all control features of
the heat pump. Even though the 55 VA transformer is
larger than the industry standard 40 VA transformer, it
can still be overloaded quickly when using it for control
equipment like zone valves or fan coil relays. Table 4
shows the transformer usage for the hydronic heat pumps.
Table 4 – Transformer Usage (VA)
Component 29-67 98, 120 380
Contactor 7 7 x 2 14 x 2
Pump Relay 3 3 N/A
Reversing Valve 4 4 9
Controller 1 1 1
Thermostat 1 1 1
Total 16 VA 23 VA 39 VA
Available 39 VA 32 VA 61 VA
If the system’s external controls require more than the VA
available for external use from the transformer, an
external transformer must be used. You can see that in
Figure 5, the heat pump’s internal transformer can easily
power the external 24-Volt system. In contrast, Figure 4
shows a fan coil system with its own power supply, which
must be coupled to the heat pump to put the heat pump
into the cooling mode. This can be accomplished using
an isolation relay which isolates the fan coil power supply
from the heat pump's transformer (e.g. use the fan coils
independent power supply to energize the coil of a relay,
passing a signal across the N.O. contacts from the heat
pump's transformer).
The heat pump's transformer can generally power simpler
control systems consisting of a few relays or zone valves
(depending, of course, on the VA draw of the
components). On more complicated control systems the
transformers capacity is used up very quickly.
)Note: For units operating on 208V electrical service,
the transformer must be switched to the correct lead (see
electrical diagram – Figures 7 and 8). Units are factory
shipped with the transformer set for 240V service.
Operating a unit on 208V with the transformer set to
240V will cause the unit to operate with lower than
normal control voltage.
B. Thermostat/Aquastat
Consult the instructions in the thermostat box for proper
mounting and thermostat operation.
, CAUTION- miswiring of control voltage on system
controls can result in transformer burnout.
)Note: If a single thermostat controls multiple heat
pumps, the control wiring of the heat pumps must be
isolated from each other. This will prevent the heat
I hate this never works